Skip to content
Battery runtimeVRLALiFePO4

UPS Battery Runtime: VRLA vs LiFePO4

How to calculate UPS battery runtime, why a simple Ah division overestimates the bank, and when LiFePO4 is worth the higher capital cost.

HENGLAN Engineering Team Battery and power systems 6 min read Published Updated
VRLA battery blocks configured for a UPS string
TL;DR

Amp-hours are not hours. Runtime is watt-hours divided by load, after about 85% inverter efficiency and 80% usable depth of discharge: a 12 V 100 Ah block holds 1.2 kWh, of which roughly 800 Wh reaches the load. VRLA is cheaper per kilowatt-hour; LiFePO4 lasts about three times as many cycles.

A UPS battery bank is often sized with a single division: load in watts, battery in amp-hours, and a result in hours. The result is usually optimistic. Batteries do not deliver their full 20-hour capacity at high current, the inverter is not 100% efficient, and the usable depth of discharge is not 100%.

This article explains the calculation, the two main chemistries, and the field checks that keep the runtime honest.

Why is runtime not a simple Ah division?

The Ah rating on a battery is usually measured at a 20-hour discharge rate. A 100 Ah block can deliver 5 A for 20 hours. At 100 A, it will not deliver 1 hour; the internal resistance and the electrochemical kinetics reduce the available capacity. The higher the current, the lower the effective capacity.

The inverter adds another loss. A 0.85 efficiency means 15% of the DC energy is lost before it reaches the load. The depth of discharge adds a third limit. A VRLA bank is typically limited to 50–60% depth of discharge for a reasonable cycle life; a LiFePO4 module can use 80–90%.

The correct method is to use the battery manufacturer’s discharge table at the expected end voltage and the expected current. The formula gives the starting point; the table gives the runtime.

How do I calculate the battery bank?

Use the simplified formula:

Ah = kW × 1,000 × hours ÷ (DC bus × inverter efficiency × usable depth of discharge)

For a 7.2 kW load, 1 hour, a 192 VDC bus, 0.85 efficiency, and 0.6 DOD, the result is about 73.5 Ah. A 16 × 12 V 100 Ah string gives 100 Ah nominal, so it covers the target with a small margin. At 2 hours, the required Ah doubles to about 147 Ah, so two strings are needed.

LoadRuntimeDC busEstimated Ah12 V 100 Ah strings
3 kW30 min72 V35 Ah1 (6 blocks)
3 kW1 h72 V69 Ah1 (6 blocks)
7.2 kW30 min192 V37 Ah1 (16 blocks)
7.2 kW1 h192 V74 Ah1 (16 blocks)
7.2 kW2 h192 V147 Ah2 (32 blocks)
14.4 kW1 h192 V147 Ah2 (32 blocks)
36 kW1 h384 V184 Ah2 (64 blocks)

The block count assumes 100 Ah blocks. A smaller block means more parallel strings; a larger block means fewer. Do not exceed the manufacturer’s recommended parallel string count.

What is the difference between VRLA and LiFePO4 runtime?

A VRLA bank is usually sized with a 50–60% usable depth of discharge. A LiFePO4 module can use 80–90%, so the same nominal energy gives more runtime. LiFePO4 also has a flatter discharge curve, so the inverter sees a more stable DC voltage through the discharge.

The capital cost is higher for LiFePO4, but the usable energy per kWh, the cycle life, and the weight are better. For a 2-hour runtime in a tight room, the lithium bank may be smaller and lighter than the lead-acid bank. For a 5-minute ride-through in a cool room, VRLA is usually the lower-cost choice.

CriterionVRLALiFePO4
Usable DOD50–60%80–90%
Cycle life300–600 at 50% DOD6,000 at 80% DOD
WeightHeavyAbout one-third
FootprintLargerSmaller
ChargerLead-acid profileLithium profile + BMS
Temperature sensitivityHighModerate
Capital costLower per kWhHigher per kWh

How does temperature change the runtime?

A battery’s available capacity falls at low temperature and its life falls at high temperature. A VRLA block at 0 °C may deliver 80–85% of its 25 °C capacity; at 40 °C it may deliver more capacity but its life is much shorter. A LiFePO4 module has a wider operating window but still needs a temperature-controlled room for the stated cycle life.

The battery room should be kept at 20–25 °C for VRLA. Every 10 °C above 25 °C roughly halves the design life. A battery that is “working” at 35 °C may fail at year 3 instead of year 8.

When should I use a lithium module?

Use LiFePO4 when the runtime is long, the room is tight, the cycle count is high, or the weight matters. A 51.2 V 100 Ah module stores about 5.12 kWh and weighs about 45 kg; a comparable lead-acid bank is much heavier and larger. For a rooftop or upper-floor room, the weight difference can decide the design.

Do not use lithium unless the UPS charger is compatible. A lead-acid charger may hold the bus at a voltage that is too high for the lithium cells, or it may not provide the correct charge profile. The BMS also needs to communicate with the UPS for full protection.

ApplicationRecommended chemistryWhy
5–15 min ride-throughVRLALower cost, simple charger
1–2 h server roomVRLA or LiFePO4Compare footprint and lifecycle
4–8 h remote siteLiFePO4Usable energy and weight
Daily cycling / solarLiFePO4Cycle life
Hot roomLiFePO4 or cooled VRLATemperature tolerance

How do I test the runtime after installation?

Run a load-bank test at the design load and measure the time to the end-of-discharge voltage. Record the battery temperature, the string voltage, and the weakest block. A UPS that reports “battery OK” may still fail under load.

Test every 12–24 months and after any deep discharge or battery replacement. If the runtime falls below the site requirement, replace the string or add capacity. Do not wait for a real outage to discover the battery is weak.

The battery checklist

  • Convert kW to Ah with the DC bus, efficiency, and usable DOD.
  • Check the high-rate discharge table; do not rely on the 20-hour rating.
  • Keep the battery room at 20–25 °C.
  • Confirm the charger current and the maximum battery size.
  • Do not mix old and new blocks in one string.
  • Use LiFePO4 only with a compatible charger and BMS.
  • Test the runtime at the design load every 12–24 months.

The battery is the part of the UPS that decides the autonomy. It deserves the same engineering attention as the UPS frame, not a last-minute line item.

FAQ

Questions from project buyers.

Project-specific answers. If your question is not here, send the load list and the site conditions.

Talk to an engineer

How do I calculate UPS battery runtime?

Use Ah = kW × 1,000 × hours ÷ (DC bus × inverter efficiency × usable depth of discharge), then check the battery’s high-rate discharge table. The formula gives a first estimate; the table gives the actual runtime.

Why is a 100 Ah battery not 100 A for one hour?

The Ah rating is usually measured at a 20-hour rate. At high current, the battery delivers less than its nominal capacity. A 100 Ah block at 100 A may last less than 45 minutes depending on the model and end voltage.

How long do VRLA batteries last?

Typically 3–5 years in a warm room and 5–10 years at 25 °C, depending on the model. Every 10 °C above 25 °C roughly halves the design life.

Is LiFePO4 a drop-in replacement for VRLA?

Only if the UPS charger has a lithium profile and the BMS can communicate with the UPS. A lead-acid charger may overcharge or undercharge a lithium module.

How much runtime can I get from a 51.2 V 100 Ah module?

It stores about 5.12 kWh. At 3 kW load and 90% inverter efficiency, the ideal runtime is about 1.5 hours; at 80% DOD, roughly 1.2 hours. Confirm the inverter cut-off and the BMS limits.

How often should I test the runtime?

Every 12–24 months at the design load, and after any deep discharge or battery replacement. A load-bank test is the only reliable check.

Next step

Send the load list. We will return the configuration.

Tell us the kW, the backup time, the phase, and the site country. You will get a capacity recommendation, a battery configuration, and the model sheet.

  • Capacity and topology recommendation
  • Battery bank and runtime estimate
  • Model sheet and commercial offer

Request a configuration and quotation

Send the load list, backup time, and site conditions. We will return a capacity recommendation, battery configuration, and commercial offer.

By submitting this form you agree to our privacy policy. Privacy policy